Calculating and sizing a current transformer

Before ordering a CT there are three calculations: the ratio, a primary current that matches the installation and the burden in VA. Ratio = rated primary / rated secondary current; a 400/5 A CT has a ratio of 80 – 200 A in the conductor gives 2.5 A at the meter. The meter multiplies readings by this CT factor unless the ratio is programmed in.

Choose the next rated value above the highest operating current; a much larger CT works mostly at part load with wider error limits.

CT factor of common ratios

RatioCT factorat 100 A in the conductor
[100/5 A](/stromwandler/100-5a)205 A
[400/5 A](/stromwandler/400-5a)801.25 A
[1000/5 A](/stromwandler/1000-5a)2000.5 A

Calculators and related pages

Recommended Products

FAQ

How do I calculate the ratio?

Rated primary current divided by rated secondary current: 400/5 A = 80.

Which primary current should I choose?

The next rated value above the highest operating current.