Current transformer 1500/5 A
Ratio 1500:5 · primary current 1500 A, secondary current 5 A
26 CELSA current transformers with a ratio of 1500/5 A: Plug-on / winding current transformers (ALO), Calibrated clip-on current transformers (ALO-E), Rail conversion current transformer (IAM, IAG) and Protective current transformer (ICM, IER-1, IER-2 …). Accuracy class 0.2, 0.2 S, 0.5, 0.5 S, 1 or 5P5–10P10, rated burden 1–45 VA. From €40.40 incl. VAT, with datasheet – order online.
26 products
Products
Frequently asked questions
What does 1500/5 A mean?
With 1500 A flowing in the primary conductor, the transformer delivers 5 A to the meter or measuring device – a ratio of 300:1. Meters and instruments are set to this CT ratio.
How much burden (VA) do I need?
The rated burden must cover the consumption of the connected devices plus the losses of the measuring line, without being much higher. The types listed here offer 1–45 VA. The VA calculator determines the value. VA calculator →
Which accuracy class?
For 1500/5 A the classes 0.2, 0.2 S, 0.5, 0.5 S, 1 and 5P5–10P10 are available here. Billing-relevant metering requires class 0.5 or better; for display and monitoring class 1 is usually sufficient. Accuracy class comparison →